MxPro 5 - General Routing InterfaceGeneral Routing Interface

The General Routing Interface General Routing interface Card is an optional module to provide fire routing outputs compliant with BS EN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1:2002

Applications / Limitations

EN54-2 compliant routing interfaces providing monitored outputs to fire alarm and routing circuits. Circuits are monitored for open and short circuit conditions in both normal and active mode - compliance with EN54-2 and BS5839-1: 2002 Clause 12.2.1a

The outputs will drive relay coils with impedances of between 1kΩ and 5kΩ.

Key Features

  • Two fire routing outputs are provided to differentiate between Call Point (MCP) and Automatic Detector (AFD) fire alarm signals if required.
  • Outputs are monitored for open and short circuit wiring issues in both the quiescent and active states, and fault conditions reported on the panel (CIE) display/LED Indicators.
  • Outputs are compatible with a wide range of routing equipment.
  • Simple to install and configure
  • Monitored outputs
  • Wide range compatibility
Specification
Output Circuit Spec.24V DC active, 5V DC monitor
Fire & Fault Outputs1.0mA monitor mode nominal, 5.0mA-25.0mA active (energised) mode dependent upon coil impendence, 40.0mA maximum short circuit.
Input Circuit Spec.4x Monitored Input - EOL 10KΩ, operating resistor 470Ω
Operating Voltage24V DC [Range 19-28V] from panel auxilliary Supply Output.
Panel Loading, standby, AC Mains fail (fault output off)43mA
Panel Loading, quiescent state (fault output on)45mA +24mA (1KΩ coil), +5mA (5KΩ coil)
Panel Loading, ALL inputs and outputs active48mA +72mA (1KΩ coils), +15mA (5kΩ coils)
On-boardIindications6x LED indicators for outputs active, communications and microprocessor heartbeat
Operating Temperature0°C to 50°C
ApprovalsBS EN54-2: 1998

Order Codes and Options

Mxp-532: General Routing Interface
Mxp-532F: General Routing Interface - Fitted

Compatibility

Can be used with all MxPro 5 series control panels programmed with version 50.07 software or later, compatible with the PC-Configuration tool from version 6.12 or later. The interface connects directly to peripheral bus connection in the panel.